Line interactive UPS is used for small business, web and departmental servers. Power-one has the complete range of Line interactive UPS from 650VA to 10kVA. Providing complete protection to your computers and electronic equipment against surges, blackouts and power fluctuation, Our UPS are your perfect choice. For equipment with larger power requirement, our Line interactive UPS system are the most reliable by providing solid battery backup to maintain sufficient power to save work when the power fails. Our Manufactured Line interactive UPS are being used by various small Industries, household works and IT Sector around the globe.
Unity power factor module
650 KVA - 10 KVATECHNICAL DATA – LINE INTERACTIVE UPS | |||||||
---|---|---|---|---|---|---|---|
Rating | |||||||
Rated Power (KVA) |
0.5 | 0.75 | 1 | 1.5 | 2 | 3 | 5 |
Active Power (kW) | 0.35 | 0.53 | 0.7 | 1.05 | 1.4 | 2.1 | 3.5 |
input | |||||||
AC Voltage | 145V TO 295V | ||||||
Phase | Single | ||||||
Frequency | 50Hz ±10% | ||||||
OUTPUT | |||||||
AC Voltage | 230V ±1% | ||||||
Phase | Single | ||||||
Frequency | 50Hz ±0.5% | ||||||
Power factor | 0.7lag | ||||||
Waveform | Modified Sine Wave | ||||||
(THD) | < 2±1% | ||||||
Transient response | ±5% for a step load of 100% | ||||||
Recovery | < 10msec | ||||||
Load crest factor | 3:1 | ||||||
BATTERY | |||||||
Battery Type | Lead acid / SMF battery | ||||||
Battery back up | 15 min to 240 min | ||||||
Protection | |||||||
Full protection | Under/Over voltage, surges, Overload, Short circuit, AC/DC fuse | ||||||
Indications | |||||||
LED | Mains ON, Mains fail, Charger ON, Inverter ON, Battery LOW | ||||||
Audio Alarm | Battery LOW, Mains fail, Inverter OVERLOAD | ||||||
Performance features | |||||||
Overload capacity | 120% for 10min, 150% for 1min | ||||||
Cooling system | Natural air | ||||||
Environment | |||||||
Temperature | 0 to 50 deg C | ||||||
Humidity | 20 to 90% non condensing | ||||||
Noise level | < 50dB |